DOC10 • Konsept Rehber

DOC10 — Cold Storage Buildings & Steel-Framed Facility Concept Guide (KS01–KS04)

Architectural layouts, dock staging corridors, and structural system comparisons for 120 m², 500 m², 1,500 m², and 4,000 m² cold storage facilities.

DOC10 Konsept Rehber
Rev. v2.0 Fiche Technique
DWG & PDF Détails CAO & Exécution
B00 Code Système Associé
DOC10 — Cold Storage Buildings & Steel-Framed Facility Concept Guide (KS01–KS04) — SerPan Cold
DOC10: Cold Storage Buildings & Steel-Framed Facility Concept Guide (KS01–KS04)
SERPAN COLD — CENTRE DE DOCUMENTATION TECHNIQUE CFY ENGINEERING

Doc ID: DOC10 | Rev: v2.0 | Engineering GSM: +90 (505) 507 04 18

DOC10

Tableau des Spécifications Techniques & Contrôles

Konsept Kodu Tipik Taban Alanı ve Operasyonel Kurgusu
KS01 — Kompakt Soğuk Oda 80–150 m² | Mevcut bina içi +2/+8°C ve -18°C ikili oda + hazırlık alanı
KS02 — Bölgesel Dağıtım Deposu 400–600 m² | 3 soğuk oda + +8°C ön koridor (sas) + 2 yükleme kapısı
KS03 — Endüstriyel İşleme & Depo 1.200–1.800 m² | Üretim, şoklama (-35°C), donmuş muhafaza ve rampa koridoru
KS04 — Lojistik Soğuk Depo Binası 3.000–5.000 m² | Yüksek tavanlı çelik karkas, raf koridorları ve çoklu tır rampası

Autres Fiches Techniques & Formulaires (DOC01 – DOC16)

SYSTÈMES DOCUMENTÉS

Produits & Détails Techniques de Notre Ligne de Production

BASE DE CONNAISSANCES TECHNIQUES (EK C)

Questions Fréquentes sur l'Ingénierie et la Fourniture

Questions techniques fréquentes sur les portes frigorifiques, le choix de l’épaisseur des panneaux, l’étanchéité et les projets clé en main.

C01 What is the difference between "Clear Opening Size" and "Wall Cut-Out Size" when ordering a cold room door?

Clear opening size is the usable internal passage width and height when the door leaf is fully open (e.g., 1200×2100 mm for pallet jacks). Wall cut-out size is the structural opening cut into the panel or masonry wall to receive the door frame, typically +70/+80 mm wider and +40/+50 mm higher depending on the frame profile.

C02 Should I choose a hinged cold room door or a sliding cold room door?

For pedestrian or hand-trolley access up to 1100 mm clear width, a hinged cold room door (D01) is ideal. Whenever pallet jacks or forklifts operate, corridors are narrow, or clear width is 1200 mm and above, a sliding cold room door (D02) should be selected to eliminate leaf sag and save corridor swing space.

C03 Why is a frame heater cable mandatory on freezer (-18°C / -25°C) and blast freezer (-35°C / -40°C) doors?

In sub-zero rooms below 0°C, moisture condenses and freezes around the perimeter gasket. An integrated frame and threshold heater cable prevents the EPDM gasket from freezing onto the aluminium frame, avoiding gasket tearing and door jamming.

C04 How is internal emergency exit safety ensured on cold room doors?

All SerPan Cold hinged and sliding cold room doors feature a standard glow-in-the-dark internal safety release handle (anti-panic mechanism) that unlocks and opens the door from the inside with a single push, even if padlocked or key-locked from outside.

C05 Should I specify a flush threshold (thresholdless) or stepped threshold door?

For any doorway used by pallet jacks, wheeled trolleys, or forklifts, a flush floor (thresholdless) configuration with a drop-seal bottom gasket is mandatory. Stepped stainless steel thresholds are only used for pedestrian-only rooms where floor panels sit above an existing slab.

C06 What technical dimensions are required when ordering a monorail cold room door (D04)?

In addition to clear door width and height, we require the monorail track height from finished floor level, track profile type (tubular or flat/I-beam), centerline offset relative to the door opening, and top slot clearance dimensions.

BUREAU D’INGÉNIERIE & DEVIS DIRECT

Sélectionnez Votre Parcours de Devis (4 Voies Techniques)

Sélectionnez le parcours adapté à votre besoin ; vos dimensions et paramètres seront transmis directement à notre bureau d’études sur WhatsApp. (+90 (505) 507 04 18)

BUREAU D’ÉTUDES SERPAN COLD

Obtenez un Devis Rapide pour Portes Frigorifiques, Panneaux ou Bâtiments Frigorifiques

Qu’il s’agisse d’une porte sur mesure, d’un lot de panneaux ou d’un entrepôt frigorifique clé en main, transmettez vos dimensions pour un chiffrage détaillé.

Fabrication Sur Mesure 60–200 mm PUR/PIR Charpente Acier SerHangar Export vers 32+ Pays
Ligne Ingénierie WhatsApp