CENTRAL RACK SYSTEMS SYSTÈMES D’INGÉNIERIE SERPAN COLD

Central Multi-Compressor Rack Refrigeration Systems

For multi-room cold storage facilities and food processing plants, central compressor racks modulate capacity dynamically across partial loads, maximizing energy efficiency and N+1 reliability.

+15°C → -40°C Chiller, Freezer & Blast Regimes
60 – 200 mm 40–42 kg/m³ PUR & PIR Core
EN 10346 & HACCP 9-Layer Hygienic Steel & Profiles
81 İl & 32+ Ülke Direct Dispatch from Gebze Hub
Central Multi-Compressor Rack Refrigeration Systems — SerPan Cold
CENTRAL RACK SYSTEMS: Central Multi-Compressor Rack Refrigeration Systems

Fiche Récapitulative Technique

CENTRAL RACK SYSTEMS
Kapasite Yönetimi
PLC Yönetimli & VFD İnvertörlü Anlık Isı Yüküne Göre Kademeli Kompresör Devreye Alma
Enerji Verimliliği
%25 – %35 Elektrik Tasarrufu Tekil Split Gruplara Kıyasla Merkezi Kondenser ve Yedekli Çalışma
Uygulama Ölçeği
500 m² – 10.000+ m² Tesisler Çok Odalı Gıda Fabrikaları, Hal Tesisleri ve 3PL Lojistik Depolar
Mühendislik Opsiyonu
Isı Geri Kazanım & Uzak Kondenser Atık Isı İle Boyler/Zemin Isıtma ve Düşük Ses Seviyesi
REFRIGERATION & AUTOMATION LINEUP

Split Units, Central Racks, Unit Coolers & Control Panels

Integrated Cold Chain Building, Panel & Door Systems

42 kg/m³ PUR / B-s1,d0 PIR sandwich panels, heavy-duty industrial cold storage doors, and central refrigeration packages manufactured at our Gebze plant.

BASE DE CONNAISSANCES TECHNIQUES (EK C)

Questions Fréquentes sur l'Ingénierie et la Fourniture

Questions techniques fréquentes sur les portes frigorifiques, le choix de l’épaisseur des panneaux, l’étanchéité et les projets clé en main.

C21 Can refrigeration capacity be calculated based solely on room volume (m³)?

No. Room volume alone only provides a preliminary estimate. Actual cooling load depends on daily product intake tonnage, product entry temperature, specific heat, pull-down time, ambient climate, and door opening frequency.

C22 Is a frozen storage room (-18°C) the same as a blast freezer room (-35°C / -40°C)?

Definitely not. A frozen storage room (-18°C) maintains products that are already frozen. A blast freezer (-35°C / -40°C) uses high-velocity airflow and high refrigeration capacity to rapidly pull down core product temperature to -18°C within hours.

C23 Should we choose individual split condensing units or a central multi-compressor rack system?

For facilities with 1 to 4 rooms or where independent redundancy per room is desired, industrial split units (R01) are cost-effective. For large multi-room logistics hubs and food factories, central multi-compressor racks (R02) offer superior energy efficiency and capacity modulation.

C24 Why is fin spacing critical when selecting cold room unit coolers (evaporators)?

While 4–6 mm fin spacing works for positive (+2/+8°C) chillers, sub-zero freezers (-18°C) require 7–8 mm and blast freezers require 10–12 mm wide fin spacing to prevent rapid frost bridging and airflow blockage.

C25 Why is remote temperature monitoring and alarm data-logging (R04) necessary?

Digital data-logging and mobile alarm panels protect high-value inventory against power outages, open doors, or defrost faults while providing mandatory historical temperature audit trails for food safety and GDP inspections.

C26 Why should an ante-room (precooling / buffer corridor) be included in cold store design?

Opening a -18°C or +2°C chamber directly to +35°C outdoor air causes severe moisture ingress, icy floors, and high power consumption. A temperature-controlled +8/+12°C ante-room acts as a thermal airlock.

BUREAU D’INGÉNIERIE & DEVIS DIRECT

Sélectionnez Votre Parcours de Devis (4 Voies Techniques)

Sélectionnez le parcours adapté à votre besoin ; vos dimensions et paramètres seront transmis directement à notre bureau d’études sur WhatsApp. (+90 (505) 507 04 18)

BUREAU D’ÉTUDES SERPAN COLD

Obtenez un Devis Rapide pour Portes Frigorifiques, Panneaux ou Bâtiments Frigorifiques

Qu’il s’agisse d’une porte sur mesure, d’un lot de panneaux ou d’un entrepôt frigorifique clé en main, transmettez vos dimensions pour un chiffrage détaillé.

Fabrication Sur Mesure 60–200 mm PUR/PIR Charpente Acier SerHangar Export vers 32+ Pays
Ligne Ingénierie WhatsApp